Contained Hot Aisle
FRAMEWORK
- The warmed air coming from the servers is blown into the contained hot aisle.
- The aisle cooling modules "ACM" extract the air from the aisle, and cool it via an air/water exchanger.
- The air flow is matched to the actual flow rate of the servers by differential pressure measurement, and the water flow is controlled at the desired output temperature.
ADVANTAGES
- Cooling systems closest to the servers
- Ability to define the level of redundancy N+1 to 2N
- The control of the air flow allows optimum operation of the servers
- Management by programmable logic controller with possible extensions in:
- ModBus RTU
- Modbus TCP/IP
- SNMP
- Dry contact
DIMENSIONAL CHARACTERISTICS
- Rack
- Height: 42 and 47U
- Depth: 1000 to 1200 mm
- Width: 600 and/or 800 mm
- ACM
Cooling Module:- L300 mm in single coil or L450 mm in dual coil
- Height: 42 and 47U
- Depth: 1000 to 1200 mm
- Containment
- Aisle width: 900 or 1200 mm
- Glass roof l 600 or 800 mm
- Full roof l 300 mm
- LED lit roof l 600 or l 800
- Manual or automatic return door
Customisation possible
Adaptation to customers' racks on request.